Design Criteria

  • To remove 55% of suspended solid and 30% of BOD5 of influent water
  • At Qp, the square overflow rate, SOR=1500 gal/ft2.day for each tank, check SOR at QA
  • Detention time DT=2.0 hr based on QA
  • Submerged orifice for inlet
  • V-notch outlet weir
  • Weir width=25'

  • For a well-designed and operated basin, the typical removal of suspended solids and BOD5 from municipal waster water as a function of overflow rate is given in Figure 11.
    TSS
    BOD5
    Removal
    Overflow rate
    Value:
    Figure 11
    Note:1 m3/m2.day=24.5424 gallon/ft2.day


    Figure 12 shows the removal of suspended solids and BOD5 with respect to detention time in primary clarifiers.
    TSS
    BOD5
    Removal
    Detention Time
    Value:
    Figure 12


    (1) Waste Water Treatment Plants, Syed R. Qasim, p268.
    (2) "The Committee of Great Lakes--Upper Mississippi River Board of State Sanitary Engineers (Ten States), Recommended Standards for Sewage Water, Health Education Service, Albany, New York, 1978.